Home › Free calculators › Batch heating and cooling time
Free calculator

Batch heating and cooling time

Time to heat or cool a batch vessel from one temperature to another, using steam, cooling water or another medium, with the temperature–time curve.

Inputs

Units:
Vessel and liquid
Heat exchanger
Temperatures
Heating / cooling medium

Results

Need this in Excel for your plant? See the PlantCalcKit Excel tools — print-ready reports, any units, visible formulas. Visit the shop →

Heat Exchanger Excel kit

Shell and tube performance, fouling, LMTD and NTU rating, condenser and reboiler performance, plate exchanger — with print-ready reports, any units and visible formulas.

Join PlantCalcKit — free

Be first to hear about new calculators, Excel tools and field guides — one short email when something new is ready. The calculators stay free with or without an account.

By joining you agree to our privacy policy. Unsubscribe or delete your details any time.

How this calculator works

When you heat or cool a batch — a tank, a reactor or a vessel — the temperature changes fastest at the start and slows as the liquid approaches the medium temperature. The time to reach a target temperature depends on the liquid's thermal mass (mass × specific heat) and the rate of heat transfer (U × A × driving force). For an isothermal medium such as condensing steam or a boiling refrigerant, the driving force decays exponentially: t = (M·Cp)/(U·A) × ln[(Ti−Tm)/(Tf−Tm)]. For a non-isothermal medium such as cooling water, the medium's own temperature changes through the exchanger, so the effective driving force is reduced by a factor K = 1 − exp(−UA/ṁCpm).

Example: 5,000 kg of water at 25 °C heated to 80 °C with steam at 150 °C through a coil with U = 500 W/m²·K and A = 10 m². Time constant = M·Cp/(U·A) = 5,000 × 4.18 / (500 × 10 / 1000) = 4,180 s (70 min). Heating time = 4,180 × ln[(25−150)/(80−150)] = 4,180 × ln(125/70) = 4,180 × 0.580 = 2,424 s (40 min). The initial duty is 5 × (150−25) = 625 kW and the final duty is 5 × (150−80) = 350 kW.

Limits: assumes perfect mixing in the vessel (uniform batch temperature), constant U and constant fluid properties. Real tanks have temperature gradients unless agitated; U can change with temperature (especially for viscous liquids); and the medium flow may vary. For accurate results on viscous or non-Newtonian fluids, use a stepwise simulation. References: Kern, Process Heat Transfer; Perry's Chemical Engineers' Handbook, Section 11.