Heat tracing heat loss and power

Heat loss per metre at the maintain temperature, design power and cable runs for electric tracing, and steam use for steam tracing, for any insulation thickness.

Inputs

Units:
Pipe and temperatures
%
Insulation
Tracing
%

Results

Need this in Excel for your plant? See the PlantCalcKit Excel tools — print-ready reports, any units, visible formulas. Visit the shop →

Join PlantCalcKit — free

Be first to hear about new calculators, Excel tools and field guides — one short email when something new is ready. The calculators stay free with or without an account.

By joining you agree to our privacy policy. Unsubscribe or delete your details any time.

How this calculator works

Heat tracing replaces the heat an insulated pipe loses, so the first number is the steady heat loss per metre with the pipe at the maintain temperature and the air at the coldest design ambient and design wind. Heat flows through the insulation, ln(Do/Dp)/(2πk) per metre, and leaves the jacket by natural convection (Churchill–Chu), wind (Churchill–Bernstein) and radiation; the calculator finds the surface temperature where these balance. Your design margin is added to give the design heat loss, and the traced length is increased by your allowance for valves, flanges and supports.

For electric tracing the total power is the design loss times the traced length; with the cable's rated output at the maintain temperature it gives the cable length per metre of pipe and the number of straight runs. For steam tracing it gives the steam temperature at the tracer pressure (it must be above the maintain temperature) and the steam condensed, design loss ÷ latent heat; with the heat delivered per metre of one tracer it gives the number of tracers. A table shows how the loss changes with insulation thickness.

Example: a 4" line (114.3 mm OD) held at 60 °C, −10 °C ambient, 5 m/s wind, 50 mm of mineral wool (k = 0.045 W/m·K) under aluminium: heat loss 30.5 W/m, 36.7 W/m with a 20 % margin. For 100 m plus 10 % allowance that is 4.03 kW; a 20 W/m cable needs 2 straight runs (220 m). With 3.5 bar g steam (148 °C) the tracers condense about 6.8 kg/h.

Method and limits

Steady state at the coldest design condition; heat-up from cold, flowing fluid and process heat gains are not counted. The insulation is taken as fitted to the pipe OD with a constant conductivity — oversized insulation around a tracer, wet or damaged insulation and gaps increase the loss. Pipe wall, inside film and the tracer air space are neglected. The margin and the allowances come from your tracing specification; cable outputs, maximum sheath temperature, hazardous-area temperature class, circuit lengths and tracer heat delivery come from the tracing maker. Steam use counts latent heat only (condensate leaving saturated) and excludes trap and distribution losses. A screening estimate, not a substitute for the tracing maker's design.

Sources

  • Heat-loss engine of the PlantCalcKit insulated pipe heat loss calculator: method basis of ASTM C680 and VDI 2055; correlations from F. P. Incropera and D. P. DeWitt, Fundamentals of Heat and Mass Transfer (Churchill–Chu, Churchill–Bernstein); Perry's §5.
  • Stefan–Boltzmann constant 5.670374 × 10⁻⁸ W/m²·K⁴ (CODATA 2018).
  • Steam saturation temperature and latent heat: IAPWS-IF97 (the PlantCalcKit steam tables engine).
  • Electric trace heating standards IEEE Std 515 and IEC/IEEE 60079-30-2 govern the items left to your specification and the cable maker; no number on this page is taken from them.